Analysis of Propane Gas Burner Experiments and FDS Simulations in a Two-Story Residential Structure with HVAC

dc.contributor.advisorMilke, Jamesen_US
dc.contributor.authorQuiat, Adamen_US
dc.contributor.departmentFire Protection Engineeringen_US
dc.contributor.publisherDigital Repository at the University of Marylanden_US
dc.contributor.publisherUniversity of Maryland (College Park, Md.)en_US
dc.date.accessioned2021-02-13T06:33:35Z
dc.date.available2021-02-13T06:33:35Z
dc.date.issued2020en_US
dc.description.abstractTo further our knowledge of fire dynamics in a residential structure with a heating, venitilation, and air conditioning (HVAC) system, a series of live fire gas burner experiments were conducted and modeling simulations were completed to compare the results. 29 full-scale experiments were conducted in a single story ranch structure on a basement with fire from a single propane fed gas burner. The structure was instrumented to measure temperatures, oxygen and carbon dioxide concentrations, water vapor concentrations, and gas velocities. In addition to the full-scale experiments, six experiments were selected and modeled for comparison. A numerical simulation program, known as a Fire Dynamics Simulator (FDS) (version 6.7.10), was used to complete the computational fluid dynamics (CFD) calculations. The FDS HVAC submodel was incorporated into the modeled experiments to compare how heat and fire gases transversed the modeled HVAC system as compared to the experimental results. Results from experimental and simulated data showed that heat and fire gases were transferred through the HVAC system during the experiments. Comparison of simulation data to the experimental data showed that FDS over predicted heat transfer through the HVAC system. However, there was sufficient agreement between data points to support FDS modeling as a more severe set of outcomes in the event of a fire.en_US
dc.identifierhttps://doi.org/10.13016/z4t3-5mgb
dc.identifier.urihttp://hdl.handle.net/1903/26719
dc.language.isoenen_US
dc.subject.pqcontrolledEngineeringen_US
dc.titleAnalysis of Propane Gas Burner Experiments and FDS Simulations in a Two-Story Residential Structure with HVACen_US
dc.typeThesisen_US

Files

Original bundle

Now showing 1 - 1 of 1
Loading...
Thumbnail Image
Name:
Quiat_umd_0117N_21211.pdf
Size:
55.13 MB
Format:
Adobe Portable Document Format