Determining the Air-Side Performance of Small-Diameter, Enhanced Tube-Fin Heat Exchangers through Numerical and Experimental Methods

Loading...
Thumbnail Image

Files

Publication or External Link

External Link to Data Files

Date

Advisor

Hwang, Yunho

Citation

Abstract

New correlations for the air-side pressure drop and heat transfer coefficient (HTC) of slit and louver fin heat exchangers with 3-5 mm outer diameter tubes were developed based on Computational Fluid Dynamics (CFD) simulations of small, symmetric fin sections using Design of Experiments (DOE) techniques. The prediction accuracy of these CFD-based correlations was validated by experimental testing of 16 unique 5 mm slit and louver fin heat exchangers under a range of air velocities. The experimental results indicate that the proposed CFD-based correlation with correction factors for air-side pressure drop can predict 100% of the experimental observations with 20% error or less. After a new data reduction procedure accounting for fin conduction was implemented and a single correction factor applied, the HTC correlations could predict 98% of accepted test data with 20% error or less regardless of fin type.