Experimental and Computational Analysis of the Fire Suppression Effectiveness of Halon 1301 Replacements
Files
Publication or External Link
Date
Authors
Advisor
Citation
DRUM DOI
Abstract
Experimental and computational work was performed to help understand why sub-inerting concentrations of HFC-125 (C2HF5) produced overpressures in the FAA aerosol can explosion test. The fire suppression performance of HCFC-123 (C2HCl2F3) was also investigated to determine whether it may perform better than HFC-125. Thermodynamic analysis shows that both agents increase the overall heat release for lean mixtures containing the aerosol can contents. HFC-125 also increases the overall reaction rate when added to lean mixtures. The overall reaction rate of mixtures containing HCFC-123 is generally lowered when sub-inerting concentrations are added. Experimental results showed that HCFC-123 has a lower minimum inerting concentration (8.9%) than HFC-125 (13.5%). Mixtures containing HCFC-123 were found to produce peak pressures in the 2 L chamber that were estimated to cause overpressures in the FAA chamber. Nitrogen dilution resulting in 20% oxygen in air was successful at eliminating the overpressure of mixtures containing HCFC-123.